Parameter Set: Fricka Calcs

CSV
Title Description Data Type Group Parameter Set(s)
ApparentLoad If HasMotorLoad is set to YES, use lookup tables. Else use value of CustomApparentLoadOverride. ELECTRICAL_APPARENT_POWER Electrical Fricka Calcs
CablingVfdToMotorSecondary Additional conductor sizes from VFD to motor. TEXT Electrical Fricka Calcs
CalcCircuitBreakerSizeMinimum [Formula] Calculates the minimum circuit breaker size based on FullLoadAmperage and sizing factors. ELECTRICAL_CURRENT Electrical Fricka Calcs
CalcConduitFill [Formula] Calculates the fill ratio of conduit based on conductor cross-sectional areas NUMBER Electrical Fricka Calcs
CalcGroundConductorArea [Formula] Calculates the ground conductor cross-section area to use in CalcConduitFill. NUMBER Electrical Fricka Calcs
CalcMinimumCircuitAmpacity [Formula] FullLoadAmperage multiplied by FactorWireSize (typically 1.25). ELECTRICAL_CURRENT Electrical Fricka Calcs
CalcParallelSet [Formula] Determines if there are parallel sets needed. TEXT Electrical Fricka Calcs
CircuitBreakerSizeStandardUnitless standard CB value divided by 1A to become just a number to use in other formulas NUMBER Electrical Fricka Calcs
ConduitSize [Formula] Gets conduit size from CalcConduitSize or CustomConduitSize. TEXT Electrical Fricka Calcs
CustomApparentLoadOverride [Override] Text value for apparent load (example: 1.92kVA) when HasApparentLoadOverride is set to YES. ELECTRICAL_APPARENT_POWER Electrical Fricka Calcs
CustomConduitSize [Override] Sets ConduitSize with text value (example: 3"C). TEXT Electrical Fricka Calcs
CustomGroundConductorSize [Override] Text value for ground conductor size (example: #10 G) when HasGroundConductorOverride is set to YES. TEXT Electrical Fricka Calcs
CustomMainCircuitBreakerSize [Override] Electrical current (example: 20.0A). ELECTRICAL_CURRENT Electrical Fricka Calcs
CustomParallelSet [Override] Number of parallel sets (example: 1). Value is only used if HasConduitWireOverride is set to YES. TEXT Electrical Fricka Calcs
CustomQuantityPhaseConductors [Override] Number of phase conductors (example: 1). Value is only used if HasConduitWireOverride is set to YES. INTEGER Electrical Fricka Calcs
DescriptionLoad Description of the electrical load. TEXT Electrical Fricka Calcs
DiconnectSwitchAmpacity Disconnect size based on minimum circuit ampacity. ELECTRICAL_CURRENT Electrical Fricka Calcs
ElectricalPhase Electrical phase value. Required because poles cannot be used in a schedule. INTEGER Electrical Fricka Calcs
ElevatorLoad Adjust Circuit Breaker, MCA, and FullLoadAmperage calculations to pull FactorCircuitBreakerSizeElevator into formulas. YESNO Electrical Fricka Calcs
FactorCircuitBreakerSizeElevator [Factor] Sizes circuit breaker for elevator loads (typically 1.4). NUMBER Electrical Fricka Calcs
FactorCircuitBreakerSizeMotor [Factor] Sizes circuit breaker for motor loads (typically 1.75 to 2). NUMBER Electrical Fricka Calcs
FactorCircuitBreakerSizeNonMotor [Factor] Sizes circuit breaker for non-motor loads (typically 1.5). NUMBER Electrical Fricka Calcs
FactorCircuitBreakerSizeVFD [Factor] Sizes circuit breaker for VFD loads (typically 1.6). NUMBER Electrical Fricka Calcs
FactorWireSize Factor for sizing the phase conductors (typically 1.25). NUMBER Electrical Fricka Calcs
FullLoadAmperage [Formula] Calculates FullLoadAmperage based on ApparentLoad, Voltage, and Phase. ELECTRICAL_CURRENT Electrical Fricka Calcs
GroundConductorSize [Formula] Gets ground conductor size based on corcuit breaker size. TEXT Electrical Fricka Calcs
HasApparentLoadOverride Override the apparent load formula and read the value of CustomApparentLoadOverride. YESNO Electrical Fricka Calcs
HasConduitWireOverride [Override] Sets ConduitSize, PhaseConductorSize, and GroundConductorSize formulas. YESNO Electrical Fricka Calcs
HasMainCircuitBreakerSizeOverride Override CalcCircuitBreakerSizeMinimum and get value of CustomMainCircuitBreakerSize. YESNO Electrical Fricka Calcs
HasMotorLoad Adjust Circuit Breaker, MCA, and FLA calculations to pull the corcuit breaker size motor factor into formulas YESNO Electrical Fricka Calcs
Horsepower Decimal value for horsepower (example: 7.500). Horsepower must be represented as decimals when required. Users must include 3 decimal points for the lookup tables to work properly. NUMBER Electrical Fricka Calcs
IsCalculateLoadVfd Adjust Circuit Breaker, MCA, and FLA calculations to pull the circuit breaker size VFD factor into formulas. YESNO Electrical Fricka Calcs
IsDisconnectSwitchRequired Use DisconnectSwitchAmpacity formula to size disconnect based on standard values. YESNO Electrical Fricka Calcs
IsNeutralRequired Add additional neutral wire to number of wires. YESNO Electrical Fricka Calcs
LoadClassification Determines what load is classified as (example: motor, power, etc.). LOADCLASSIFICATION Electrical Fricka Calcs
LookupCircuitBreakerMotor [Lookup] Gets the circuit breaker size for motor equipment. TEXT Electrical Fricka Calcs
LookupCircuitBreakerNonMotor [Lookup] Gets the circuit breaker size for non-motor equipment. TEXT Electrical Fricka Calcs
LookupConductorArea [Lookup] Gets phase conductor cross-sectional area. TEXT Electrical Fricka Calcs
LookupGroundConductor [Lookup] Gets ground conductor size. TEXT Electrical Fricka Calcs
LookupGroundConductorArea [Lookup] Gets ground conductor cross-sectional area. TEXT Electrical Fricka Calcs
LookupMotor120v1phase [Lookup] For 120V, 1 phase motors. TEXT Electrical Fricka Calcs
LookupMotor208v1phase [Lookup] For 208V, 1 phase motors. TEXT Electrical Fricka Calcs
LookupMotor208v3phase [Lookup] For 208V, 3 phase motors. TEXT Electrical Fricka Calcs
LookupMotor480v3phase [Lookup] For 480V, 3 phase motors. TEXT Electrical Fricka Calcs
LookupParallelSet [Lookup] Gets parallel set requirements for motor equipment. TEXT Electrical Fricka Calcs
LookupParallelSetNonMotor [Lookup] Gets parallel set requirements for non-motor equipment. TEXT Electrical Fricka Calcs
LookupSizeConduit [Lookup] Gets conduit size. TEXT Electrical Fricka Calcs
MinimumCircuitAmpacityUnitless minimum circuit ampacity divided by 1A; number to be used in other formulas NUMBER Electrical Fricka Calcs
PhaseConductorArea [Formula] Gets the phase conductor area to provide for CalcConduitFill. NUMBER Electrical Fricka Calcs
PhaseConductorSize [Formula] Gets phase conductor size based on a lookup table. TEXT Electrical Fricka Calcs